Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 31, 2019, 09:09 AM
  • F 0060_F 0059 _103119_021013.mp4

Date
10/31/2019
W/O
792836
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00035
PipeID
P10145
Time
2:09 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7081
Sewer Name
F JOINT OUTFALL F - UNIT 3A
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Routine Assessment
Project
WO_792836_TV02235_OCT2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Width
60 in.
Upstream MH
F 0060
Downstream MH
F 0059
Dir. of Survey
Downstream
Length Surveyed
261.6 ft.
Total Length
261.6 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole F 0060 to F 0059
MH: F 0060MH: F 0059downstream0 ft. MWL - Water Level, 45 %of cross sectional area0 ft. MWM - Water Mark, 65 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - F 00602.6 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start6.6 ft. MGO - General Observation - MAG COAT THROUGHOUT14.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start258.9 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish259.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish261.6 ft. AMH - Downstream Manhole, Survey Ends - F 0059

Observation photos (2)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    14.9 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
259.2SSS
0MWL
261.6AMHF 0059
258.9SAP
2.6SAP
14.9SSS
0MWM
0AMHF 0060
6.6MGOMAG COAT THROUGHOUT

Properties (6)

additional_info
SC378681
custom_field_two
3
customer
LACSD
datetime
2019-10-31T02:09:22-07:00
documentation
PROPIPE
is_lateral_inspection
false