Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 5, 2019, 09:46 AM
  • F 0059_F 0058 _11052019_021305.mp4

Date
11/05/2019
W/O
792836
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00035
PipeID
P10144
Time
1:46 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7085
Sewer Name
F JOINT OUTFALL F - UNIT 3A
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Routine Assessment
Project
WO_792836_TV02235_OCT2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Width
60 in.
Upstream MH
F 0059
Downstream MH
F 0058
Dir. of Survey
Downstream
Length Surveyed
599.6 ft.
Total Length
599.6 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole F 0059 to F 0058
MH: F 0059MH: F 0058downstream0 ft. AMH - Upstream Manhole, Survey Begins - F 00590 ft. MWL - Water Level, 60 %of cross sectional area0 ft. MWM - Water Mark, 80 %of cross sectional area10 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start10 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start10 ft. MGO - General Observation - MAG COAT THROUGHOUT597.9 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish597.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish599.6 ft. AMH - Downstream Manhole, Survey Ends - F 0058

Observation photos (2)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    10 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    10 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
10SAP
10SSS
0AMHF 0059
597.9SAP
0MWL
597.9SSS
10MGOMAG COAT THROUGHOUT
599.6AMHF 0058
0MWM

Properties (6)

additional_info
SC378685
custom_field_two
3
customer
LACSD
datetime
2019-11-05T01:46:18-08:00
documentation
PROPIPE
is_lateral_inspection
false