Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 6, 2019, 09:53 AM
  • F 0050_F 0049 _11062019_020719.mp4

Date
11/06/2019
W/O
792836
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00035
PipeID
P10135
Time
1:53 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7086
Sewer Name
F JOINT OUTFALL F - UNIT 3A
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Routine Assessment
Project
WO_792836_TV02235_OCT2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Width
60 in.
Upstream MH
F 0050
Downstream MH
F 0049
Dir. of Survey
Downstream
Length Surveyed
460.1 ft.
Total Length
460.1 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole F 0050 to F 0049
MH: F 0050MH: F 0049downstream0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - F 00500 ft. MWM - Water Mark, 75 %of cross sectional area2.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAG COAT THROUGHOUT2.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start457.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish457.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish460.1 ft. AMH - Downstream Manhole, Survey Ends - F 0049

Observation photos (2)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
2.1SAP
0MWL
0AMHF 0050
2.1MGOMAG COAT THROUGHOUT
0MWM
460.1AMHF 0049
2.1SSS
457.4SAP
457.4SSS

Properties (6)

additional_info
SC378686
custom_field_two
3
customer
LACSD
datetime
2019-11-06T01:53:39-08:00
documentation
PROPIPE
is_lateral_inspection
false