Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 8, 2019, 06:18 AM
  • F 0046_F 0045 _11072019_222931.mp4

Date
11/07/2019
W/O
792836
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00035
PipeID
P10131
Time
10:18 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7156
Sewer Name
F JOINT OUTFALL F - UNIT 3A
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Routine Assessment
Project
WO_792836_TV02235_OCT2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Width
60 in.
Upstream MH
F 0046
Downstream MH
F 0045
Dir. of Survey
Downstream
Length Surveyed
384.2 ft.
Total Length
384.2 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole F 0046 to F 0045
MH: F 0046MH: F 0045downstream0 ft. MWL - Water Level, 60 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Ends - F 00460.8 ft. MWM - Water Mark, 75 %of cross sectional area2.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.5 ft. MGO - General Observation - MAG COAT THROUGHOUT382.5 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish384.2 ft. AMH - Downstream Manhole, Survey Ends - F 0045

Observation photos (1)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
2.5MGOMAG COAT THROUGHOUT
2.2SAP
0.8MWM
0MWL
0AMHF 0046
384.2AMHF 0045
382.5SAP

Properties (6)

additional_info
SC378691
custom_field_two
3
customer
LACSD
datetime
2019-11-07T22:18:23-08:00
documentation
PROPIPE
is_lateral_inspection
false