Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 21, 2019, 09:50 AM
  • 01 0564A_01 0564_02212019_023524.mp4

Date
02/21/2019
W/O
750737
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00194
PipeID
P01052
Time
1:50 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6280
Sewer Name
01 ALAMEDA STREET EXTENSION TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_750737_TV01001_FEB2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
01 0564A
Downstream MH
01 0564
Dir. of Survey
Downstream
Length Surveyed
8.2 ft.
Total Length
8.2 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 01 0564A to 01 0564
MH: 01 0564AMH: 01 0564downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 0564A0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/UNKNOWN2.6 ft. MGO - General Observation - 85% MAG COAT6.4 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - UNKNOWN DEBRIS IN LINE8.2 ft. MSA - Survey Abandoned - DUE TO DEBRIS IN LINE

Observation photos (1)

  • Deposits Settled Other,  10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES - UNKNOWN DEBRIS IN LINE

    6.4 ft. - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - UNKNOWN DEBRIS IN LINE

Observations (7)

DistanceCodeObservation
0MWL
0MWM
0AMH01 0564A
2.6MGO85% MAG COAT
0MGOCONN @ MH 9 O'CLOCK/UNKNOWN
8.2MSADUE TO DEBRIS IN LINE
6.4DSZUNKNOWN DEBRIS IN LINE

Properties (5)

custom_field_two
5
customer
LACSD
datetime
2019-02-21T01:50:58-08:00
documentation
PROPIPE
is_lateral_inspection
false