Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 14, 2019, 07:44 PM
  • 16 0368_16 0367 _11142019_115936.mp4

Date
11/14/2019
W/O
792820
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00665
PipeID
P13419
Time
11:44 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6822
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
SAN MARINO
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_792820_TV16061_OCT2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
16 0368
Downstream MH
16 0367
Dir. of Survey
Downstream
Length Surveyed
195.6 ft.
Total Length
195.6 ft.
Structural Index
4
Structural Quick
4100
Structural Rating
4
O&M Index
3
O&M Quick
4132
O&M Rating
11
Overall Index
3
Overall Quick
Overall Rating
15
Pipe schematic from manhole 16 0368 to 16 0367
MH: 16 0368MH: 16 0367downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 03682.6 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES10.2 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start10.2 ft. RFJ - Roots Fine Joint, from 12 to 03 o'clock, within 8 inches of joint: YES13.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"112.5 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"172.6 ft. RMC - Roots Medium Connection, at 12 o'clock, 10 %, within 8 inches of joint: YES173.4 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"173.4 ft. RBL - Roots Ball Lateral, at 12 o'clock, 85 %194 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish195.6 ft. AMH - Downstream Manhole, Survey Ends - 16 0367

Observation photos (5)

  • Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES

    2.6 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    10.2 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 12 to 03 o'clock, within 8 inches of joint: YES

    10.2 ft. - Roots Fine Joint, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Roots Medium Connection, at 12 o'clock, 10 %, within 8 inches of joint: YES

    172.6 ft. - Roots Medium Connection, at 12 o'clock, 10 %, within 8 inches of joint: YES

  • Roots Ball Lateral, at 12 o'clock, 85 %

    173.4 ft. - Roots Ball Lateral, at 12 o'clock, 85 %

Observations (13)

DistanceCodeObservation
13.8TF
112.5TB
195.6AMH16 0367
172.6RMC
2.6DAGS
10.2FM
10.2RFJ
194FM
0MWL
0MWM
173.4TB
0AMH16 0368
173.4RBL

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-11-14T11:44:47-08:00
documentation
PRO PIPE
is_lateral_inspection
false