Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 30, 2019, 06:09 AM
  • 16 0353_16 0352 _10292019_222541.mp4

Date
10/29/2019
W/O
792820
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00665
PipeID
P13404
Time
11:09 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7095
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_792820_TV16061_OCT2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
14 in.
Width
14 in.
Upstream MH
16 0353
Downstream MH
16 0352
Dir. of Survey
Downstream
Length Surveyed
282 ft.
Total Length
282 ft.
Structural Index
4
Structural Quick
4J3J
Structural Rating
392
O&M Index
2
O&M Quick
2U19
O&M Rating
233
Overall Index
3
Overall Quick
Overall Rating
625
Pipe schematic from manhole 16 0353 to 16 0352
MH: 16 0353MH: 16 0352downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 03530 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start - POSSIBLE MINERAL OR PIPE DISCOLORATION3.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"9.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"102.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"104.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"132.9 ft. RFJ - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR155.8 ft. RFJ - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR160.6 ft. RFJ - Roots Fine Joint, from 04 to 08 o'clock, within 8 inches of joint: YESR163.3 ft. RFJ - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR203.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"205.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"255.1 ft. RFJ - Roots Fine Joint, from 04 to 08 o'clock, within 8 inches of joint: YESR, Start278 ft. RFJ - Roots Fine Joint, from 04 to 08 o'clock, within 8 inches of joint: YESR, Finish281.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish281.4 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish - POSSIBLE MINERAL OR PIPE DISCOLORATION281.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish282 ft. AMH - Downstream Manhole, Survey Ends - 16 0352282 ft. MGO - General Observation - DAMAGED TROUGH.

Observation photos (9)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start -  POSSIBLE MINERAL OR PIPE DISCOLORATION

    2 ft. - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start - POSSIBLE MINERAL OR PIPE DISCOLORATION

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR

    132.9 ft. - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR

  • Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR

    155.8 ft. - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR

  • Roots Fine Joint, from 04 to 08 o'clock, within 8 inches of joint: YESR

    160.6 ft. - Roots Fine Joint, from 04 to 08 o'clock, within 8 inches of joint: YESR

  • Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR

    163.3 ft. - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR

  • Roots Fine Joint, from 04 to 08 o'clock, within 8 inches of joint: YESR, Start

    255.1 ft. - Roots Fine Joint, from 04 to 08 o'clock, within 8 inches of joint: YESR, Start

  • General Observation - DAMAGED TROUGH.

    282 ft. - General Observation - DAMAGED TROUGH.

Observations (23)

DistanceCodeObservation
2DAGS
102.3TFA
281.4DAGS
9.7TFA
163.3RFJ
104.9TFA
0AMH16 0353
278RFJ
160.6RFJ
2DAZPOSSIBLE MINERAL OR PIPE DISCOLORATION
255.1RFJ
281.4DAZPOSSIBLE MINERAL OR PIPE DISCOLORATION
132.9RFJ
7.4TFA
203.1TFC
155.8RFJ
282AMH16 0352
0MWM
281.9FM
282MGODAMAGED TROUGH.
0MWL
3.4FM
205.3TFA

Properties (6)

additional_info
SC378730
custom_field_two
2
customer
LACSD
datetime
2019-10-29T23:09:18-07:00
documentation
PRO PIPE
is_lateral_inspection
false