Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 1, 2019, 08:51 AM
  • 16 0324_16 0323 _11012019_010626.mp4

Date
11/01/2019
W/O
792820
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00665
PipeID
P13375
Time
1:51 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7107
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
ALHAMBRA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_792820_TV16061_OCT2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
16 0324
Downstream MH
16 0323
Dir. of Survey
Downstream
Length Surveyed
283.6 ft.
Total Length
283.6 ft.
Structural Index
4
Structural Quick
4J3J
Structural Rating
385
O&M Index
2
O&M Quick
2U11
O&M Rating
225
Overall Index
3
Overall Quick
Overall Rating
610
Pipe schematic from manhole 16 0324 to 16 0323
MH: 16 0324MH: 16 0323downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 16 03240 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start - MINERAL3.9 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start23.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"25.4 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"73.1 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"75.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"119.3 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"119.3 ft. RFL - Roots Fine Lateral, from 01 to 03 o'clock120.8 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"122.9 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"170.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"172.9 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"220.7 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"223.2 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"268 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"273 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"281.3 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish281.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE281.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish281.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish283.6 ft. AMH - Downstream Manhole, Survey Ends - 16 0323

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Other, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start - MINERAL

    2 ft. - Deposits Attached Other, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start - MINERAL

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Lateral, from 01 to 03 o'clock

    119.3 ft. - Roots Fine Lateral, from 01 to 03 o'clock

  • General Observation - COCKROACHES IN MANHOLE

    281.3 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (26)

DistanceCodeObservation
122.9TFC
0MGOCOCKROACHES IN MANHOLE
283.6AMH16 0323
273TFC
281.3DAZ
23.4TFA
2DAGS
281.3MGOCOCKROACHES IN MANHOLE
268TFC
220.7TFA
0AMH16 0324
223.2TFC
170.6TFA
73.1TFC
25.4TFC
119.3TBA
3.9FM
0MWM
120.8TFA
2DAZMINERAL
281.3DAGS
281.3FM
119.3RFL
172.9TFC
0MWL
75.9TFA

Properties (6)

additional_info
SC378738
custom_field_two
2
customer
LACSD
datetime
2019-11-01T01:51:00-07:00
documentation
PRO PIPE
is_lateral_inspection
false