Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 1, 2019, 09:07 AM
  • 16 0323_16 0322 _11012019_011918.mp4

Date
11/01/2019
W/O
792820
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00665
PipeID
P13374
Time
2:07 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7107
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
ALHAMBRA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_792820_TV16061_OCT2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
16 0323
Downstream MH
16 0322
Dir. of Survey
Downstream
Length Surveyed
221.7 ft.
Total Length
221.7 ft.
Structural Index
3
Structural Quick
3H00
Structural Rating
129
O&M Index
2
O&M Quick
2H12
O&M Rating
88
Overall Index
2
Overall Quick
Overall Rating
217
Pipe schematic from manhole 16 0323 to 16 0322
MH: 16 0323MH: 16 0322downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 03232 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start34 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"37.4 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"58 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"84.3 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"131.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"134 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"179.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"179.2 ft. RFL - Roots Fine Lateral, from 01 to 03 o'clock182 ft. RFL - Roots Fine Lateral, from 10 to 11 o'clock182 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"219.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish219.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish220.4 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 8 O'CLOCK221.7 ft. AMH - Downstream Manhole, Survey Ends - 16 0322221.7 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Lateral, from 01 to 03 o'clock

    179.2 ft. - Roots Fine Lateral, from 01 to 03 o'clock

  • General Observation - COCKROACHES IN MANHOLE

    221.7 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (21)

DistanceCodeObservation
219.3CM
182RFL
220.4MGOACTIVE CONNECTION AT MH 8 O'CLOCK
37.4TFA
34TF
0MGOCOCKROACHES IN MANHOLE
84.3TFC
134TFC
0MWL
179.2TFA
58TF
0MWM
182TFA
2DAGS
221.7AMH16 0322
219.3DAGS
131.3TFA
3.9CM
221.7MGOCOCKROACHES IN MANHOLE
179.2RFL
0AMH16 0323

Properties (6)