Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 8, 2019, 10:21 AM
  • 16 0312_16 0311 _11082019_023042.mp4

Date
11/08/2019
W/O
792820
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00665
PipeID
P13363
Time
2:21 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7116
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
ALHAMBRA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_792820_TV16061_OCT2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
16 0312
Downstream MH
16 0311
Dir. of Survey
Downstream
Length Surveyed
176.7 ft.
Total Length
176.7 ft.
Structural Index
3
Structural Quick
3B21
Structural Rating
41
O&M Index
2
O&M Quick
312F
O&M Rating
71
Overall Index
2
Overall Quick
Overall Rating
112
Pipe schematic from manhole 16 0312 to 16 0311
MH: 16 0312MH: 16 0311downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 03122 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"10.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"48.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"72.2 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES92.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"92.7 ft. RML - Roots Medium Lateral, from 01 to 04 o'clock, 10 %, within 8 inches of joint: YES99.8 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES112.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start148.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"151.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"174.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish174.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish176.7 ft. AMH - Downstream Manhole, Survey Ends - 16 0311

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    72.2 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Roots Medium Lateral, from 01 to 04 o'clock, 10 %, within 8 inches of joint: YES

    92.7 ft. - Roots Medium Lateral, from 01 to 04 o'clock, 10 %, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    99.8 ft. - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    112.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
148.9TFA
48.9TFC
92.7TFA
10.5TFA
174.3CM
0MWM
151.4TFC
99.8CM
174.3DAGS
0MWL
112.3CM
0AMH16 0312
72.2CL
2.5TFC
2DAGS
92.7RML
176.7AMH16 0311

Properties (6)

additional_info
SC378747
custom_field_two
3
customer
LACSD
datetime
2019-11-08T02:21:48-08:00
documentation
PRO PIPE
is_lateral_inspection
false