Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 5, 2019, 07:14 AM
  • 20 0333_20 0332_11042019_233347.mp4

Date
11/04/2019
W/O
792787
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00755
PipeID
P19282
Time
11:14 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7110
Sewer Name
20 45TH STREET EAST TRUNK
City
PALMDALE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 20
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_792787_TV20061_OCT2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
20 0333
Downstream MH
20 0332
Dir. of Survey
Downstream
Length Surveyed
438.5 ft.
Total Length
438.5 ft.
Structural Index
3
Structural Quick
3P21
Structural Rating
263
O&M Index
2
O&M Quick
412Q
O&M Rating
181
Overall Index
2
Overall Quick
Overall Rating
444
Pipe schematic from manhole 20 0333 to 20 0332
MH: 20 0333MH: 20 0332downstream0 ft. AMH - Upstream Manhole, Survey Begins - 20 03330 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 35 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start11.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"35.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"59.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"84 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"111.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"136.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"159.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"184.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"208.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"236.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"260.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"284.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"309.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"333.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"347.7 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES347.7 ft. RFJ - Roots Fine Joint, at 02 o'clock, within 8 inches of joint: YESR361.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"385.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"409.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"430.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"437 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish437 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish438 ft. VR - Vermin - Rat, within 8 inches of joint: NO, 1438.5 ft. AMH - Downstream Manhole, Survey Ends - 20 0332

Observation photos (3)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 02 o'clock, within 8 inches of joint: YESR

    347.7 ft. - Roots Fine Joint, at 02 o'clock, within 8 inches of joint: YESR

Observations (29)

DistanceCodeObservation
2SAP
347.7CL
11.2TFC
84TFC
111.8TFC
409.8TFC
437SAP
361.4TFC
184.4TFC
35.4TFC
136.1TFC
236.4TFC
59.5TFC
159.8TFC
437DAGS
438VR
385.5TFC
347.7RFJ
0AMH20 0333
333.3TFC
208.3TFC
2DAGS
438.5AMH20 0332
0MWM
260.9TFC
0MWL
284.6TFC
430.2TFC
309.5TFC

Properties (6)

additional_info
SC378741
custom_field_two
2
customer
LACSD
datetime
2019-11-04T23:14:39-08:00
documentation
PRO PIPE
is_lateral_inspection
false