- Date
- 10/28/2019
- W/O
- 792802
- Weather
- Dry
- Operator/Surveyor
- J. BUENROSTRO
- Sewer ID
- Z00003
- PipeID
- P00435
- Time
- 10:45 PM
- Certificate
- U-715-07000770
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K7076
- Sewer Name
- 08 DAVIDSON CITY TRUNK, SECTS 1,2,&3
- City
- CARSON
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 08
- Page No.
- 12
- Purpose
- Routine Assessment
- Project
- RFIR_WO_792802_TV08178_OCT2019
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 18 in.
- Width
- 18 in.
- Upstream MH
- 08 0383
- Downstream MH
- 08 0382
- Dir. of Survey
- Downstream
- Length Surveyed
- 417.2 ft.
- Total Length
- 417.2 ft.
- Structural Index
- 3
- Structural Quick
- 3322
- Structural Rating
- 13
- O&M Index
- 2
- O&M Quick
- 2500
- O&M Rating
- 10
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 23
Pipe schematic from manhole 08 0383 to 08 0382 Observation photos (6)

6.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

6.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

83.9 ft. - Crack Multiple, from 06 to 12 o'clock, within 8 inches of joint: YES

231.5 ft. - Crack Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES

282.9 ft. - Fracture Spiral, from 12 to 04 o'clock, within 8 inches of joint: YES

328.9 ft. - Crack Spiral, from 12 to 05 o'clock, within 8 inches of joint: YES