Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 11, 2019, 10:23 AM
  • 02 1794_02 1793_10112019_024529.mp4

Date
10/11/2019
W/O
792822
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00292
PipeID
P04139
Time
3:23 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7060
Sewer Name
02 MONTEREY PARK RELIEF TRUNK
City
EAST LOS ANGELES
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_792822_TV02215_OCT2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
02 1794
Downstream MH
02 1793
Dir. of Survey
Downstream
Length Surveyed
324.7 ft.
Total Length
324.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 02 1794 to 02 1793
MH: 02 1794MH: 02 1793downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 17940 ft. MWL - Water Level, 10 %of cross sectional area2.3 ft. MGO - General Observation - LINED PIPE6.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - UNKNOWN22 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - UNKNOWN26.6 ft. DSC - Deposits Settled Compacted, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO42.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - UNKNOWN, OPEN60.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - UNKOWN, OPEN91 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - UNKNOWN, OPEN102.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - UNKNOWN, OPEN129.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - UNKNOWN, OPEN141.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE177.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - UNKNOWN, OPEN184.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN, UNKNOWN213.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN, UNKNOWN219.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN, UNKNOWN264.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN, UNKNOWN270.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN, UNKNOWN276.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN, UNKNOWN283 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE324.6 ft. MGO - General Observation - DROP CONNECTION PLUGGED UP324.7 ft. AOC - Drop Connection, Survey Ends - 02 1793

Observation photos (2)

  • Deposits Settled Compacted,  15 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO

    26.6 ft. - Deposits Settled Compacted, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO

  • General Observation - DROP CONNECTION PLUGGED UP

    324.6 ft. - General Observation - DROP CONNECTION PLUGGED UP

Observations (23)

DistanceCodeObservation
213.5TFOPEN, UNKNOWN
6.1TFUNKNOWN
283TFACTIVE
177.6TFUNKNOWN, OPEN
324.6MGODROP CONNECTION PLUGGED UP
276.9TFOPEN, UNKNOWN
184.7TFOPEN, UNKNOWN
2.3MGOLINED PIPE
270.9TFOPEN, UNKNOWN
129.3TFUNKNOWN, OPEN
141.5TFACTIVE
26.6DSC
324.7AOC02 1793
0MWM
60.5TFUNKOWN, OPEN
102.5TFUNKNOWN, OPEN
0AMH02 1794
22TFUNKNOWN
0MWL
42.2TFUNKNOWN, OPEN
219.2TFOPEN, UNKNOWN
264.6TFOPEN, UNKNOWN
91TFUNKNOWN, OPEN

Properties (6)

additional_info
SC378660
custom_field_two
4
customer
LACSD
datetime
2019-10-11T03:23:40-07:00
documentation
PROPIPE
is_lateral_inspection
false