Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 13, 2019, 08:08 AM
  • 05 0870_05 0869 _06132019_015208.mp4

Date
06/13/2019
W/O
766396
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00457
PipeID
P06101
Time
1:08 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6600
Sewer Name
05 IMPERIAL HIGHWAY EXTENSION TRUNK
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
12
Purpose
Routine Assessment
Project
WO_766396_TV05196_MAY2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
05 0870
Downstream MH
05 0869
Dir. of Survey
Downstream
Length Surveyed
330.6 ft.
Total Length
330.6 ft.
Structural Index
4
Structural Quick
4434
Structural Rating
28
O&M Index
2
O&M Quick
2211
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
33
Pipe schematic from manhole 05 0870 to 05 0869
MH: 05 0870MH: 05 0869downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 08700 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. VC - Vermin Cockroach2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start57.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"60.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"120.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"121.7 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES122.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"123.9 ft. FM - Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES188.4 ft. FS - Fracture Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES189.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"190.8 ft. CM - Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES191.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"240.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"241.8 ft. FM - Fracture Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES242.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"290.1 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES291 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"292.7 ft. CM - Crack Multiple, from 04 to 06 o'clock, within 8 inches of joint: YES293.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"325.7 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES327.8 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish327.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish330.6 ft. MGO - General Observation - ABANDONED MH330.6 ft. AMH - Downstream Manhole, Survey Ends - 05 0869

Observation photos (10)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    121.7 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

    123.9 ft. - Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

    188.4 ft. - Fracture Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

    190.8 ft. - Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

    241.8 ft. - Fracture Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    290.1 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 04 to 06 o'clock, within 8 inches of joint: YES

    292.7 ft. - Crack Multiple, from 04 to 06 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    325.7 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

Observations (28)

DistanceCodeObservation
191.8TF
120.5TF
57.5TF
330.6MGOABANDONED MH
2DAGS
327.8DAE
123.9FM
122.7TF
188.4FS
240.3TF
330.6AMH05 0869
189.3TF
121.7FM
291TF
60.9TF
242.9TF
0AMH05 0870
0MWL
2DAE
325.7CM
290.1FM
0MWM
241.8FM
293.5TF
190.8CM
292.7CM
0VC
327.8DAGS

Properties (6)

additional_info
SC377530
custom_field_two
2
customer
LACSD
datetime
2019-06-13T01:08:55-07:00
documentation
ProPipe
is_lateral_inspection
false