Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 14, 2019, 07:27 PM
  • 16 0369_16 0368 _11142019_114029.mp4

Date
11/14/2019
W/O
742114
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00665
PipeID
P13420
Time
11:27 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6821
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
SAN MARINO
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
17
Purpose
Routine Assessment
Project
WO_742114_TV16032_OCT2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Width
16 in.
Upstream MH
16 0369
Downstream MH
16 0368
Dir. of Survey
Downstream
Length Surveyed
234.1 ft.
Total Length
234.1 ft.
Structural Index
4
Structural Quick
4300
Structural Rating
12
O&M Index
3
O&M Quick
3200
O&M Rating
6
Overall Index
4
Overall Quick
Overall Rating
18
Pipe schematic from manhole 16 0369 to 16 0368
MH: 16 0369MH: 16 0368downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 03699 ft. FM - Fracture Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES14.3 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES19.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start73.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"197.8 ft. RMC - Roots Medium Connection, from 02 to 03 o'clock, 15 %, within 8 inches of joint: YES199.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"232.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish234.1 ft. AMH - Downstream Manhole, Survey Ends - 16 0368

Observation photos (4)

  • Fracture Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

    9 ft. - Fracture Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    14.3 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    19.3 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Connection, from 02 to 03 o'clock, 15 %, within 8 inches of joint: YES

    197.8 ft. - Roots Medium Connection, from 02 to 03 o'clock, 15 %, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
0MWL
0MWM
73.8TF
197.8RMC
14.3FM
19.3FM
232.3FM
9FM
0AMH16 0369
199.3TB
234.1AMH16 0368

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-11-14T11:27:37-08:00
documentation
PRO PIPE
is_lateral_inspection
false