Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 13, 2019, 10:51 AM
  • 16 0300_16 0299 _11132019_030750.mp4

Date
11/13/2019
W/O
742114
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00665
PipeID
P13351
Time
2:51 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6335
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
ALHAMBRA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
21
Purpose
Routine Assessment
Project
WO_742114_TV16032_OCT2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
22 in.
Width
22 in.
Upstream MH
16 0300
Downstream MH
16 0299
Dir. of Survey
Downstream
Length Surveyed
366.9 ft.
Total Length
366.9 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
2
Overall Quick
Overall Rating
5
Pipe schematic from manhole 16 0300 to 16 0299
MH: 16 0300MH: 16 0299downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 03000 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area23.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"23.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"27.6 ft. RFC - Roots Fine Connection, at 10 o'clock27.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"29.8 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES40.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"61.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"65.8 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES76 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"127.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"132.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"160.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"178.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"203.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"219.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"275.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"283.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"298.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"298.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"315.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"315.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"347.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"366.9 ft. AMH - Downstream Manhole, Survey Ends - 16 0299366.9 ft. MGO - General Observation - CONNECTION AT 9 O'CLOCK

Observation photos (1)

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    29.8 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

Observations (27)

DistanceCodeObservation
65.8CL
127.3TF
298.1TFC
160.8TF
203.8TF
366.9AMH16 0299
40.3TF
283.1TF
298.1TF
0AMH16 0300
347.7TF
27.6RFC
0MWM
27.6TF
23.9TFC
275.5TF
178.3TF
219.3TF
315.8TF
315.9TFC
0MWL
76TF
61.8TFC
29.8CL
23.9TF
132.4TF
366.9MGOCONNECTION AT 9 O'CLOCK

Properties (6)

additional_info
SC365778
custom_field_two
4
customer
LACSD
datetime
2019-11-13T02:51:25-08:00
documentation
PROPIPE
is_lateral_inspection
false