Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 14, 2019, 07:55 AM
  • 16 0299_16 0298 _11132019_235751.mp4

Date
11/13/2019
W/O
742114
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00665
PipeID
P13350
Time
11:55 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6337
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
ALHAMBRA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
21
Purpose
Routine Assessment
Project
WO_742114_TV16032_OCT2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
22 in.
Width
22 in.
Upstream MH
16 0299
Downstream MH
16 0298
Dir. of Survey
Downstream
Length Surveyed
361.6 ft.
Total Length
361.6 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
183
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
183
Pipe schematic from manhole 16 0299 to 16 0298
MH: 16 0299MH: 16 0298downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 02990 ft. MWL - Water Level, 10 %of cross sectional area8.6 ft. CM - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES24.3 ft. CM - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES65.1 ft. CM - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES70.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start149.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"197.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"200.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"252 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"358.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish360.7 ft. MGO - General Observation - CONNECTION AT 3 O'CLOCK361.6 ft. AMH - Downstream Manhole, Survey Ends - 16 0298

Observation photos (4)

  • Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

    8.6 ft. - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

    24.3 ft. - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    65.1 ft. - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    70.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
24.3CM
0MWM
149.4TF
358.8CM
360.7MGOCONNECTION AT 3 O'CLOCK
361.6AMH16 0298
70.2CM
252TFC
0AMH16 0299
8.6CM
200.9TF
0MWL
65.1CM
197.7TFC

Properties (6)

additional_info
SC365780
custom_field_two
3
customer
LACSD
datetime
2019-11-13T23:55:09-08:00
documentation
PROPIPE
is_lateral_inspection
false