Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 19, 2019, 07:07 AM
  • 05 0899_05 0898 _11182019_233127.mp4

Date
11/18/2019
W/O
792769
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00512
PipeID
P06129
Time
11:07 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7166
Sewer Name
05 RAYMOND AVENUE TRUNK
City
HAWTHORNE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_792796_TV05204_OCT2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
05 0899
Downstream MH
05 0898
Dir. of Survey
Downstream
Length Surveyed
321.6 ft.
Total Length
321.6 ft.
Structural Index
3
Structural Quick
443L
Structural Rating
325
O&M Index
2
O&M Quick
312L
O&M Rating
131
Overall Index
2
Overall Quick
Overall Rating
456
Pipe schematic from manhole 05 0899 to 05 0898
MH: 05 0899MH: 05 0898downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 08990 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start19.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start23.4 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - BROKEN CONNECTION70.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - UNKNOWN84 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start84.6 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6"87.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"87.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish120.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"131.1 ft. FM - Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: NO - AT CONNECTION131.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"150.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"166 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"178.1 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"211.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"226.6 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"242.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"262.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"292.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"295.4 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"305.9 ft. TBI - Tap Break-In Intruding, at 01 o'clock, -, -, within 8 inches of joint: NO, 6", 1"317.2 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES319.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish319.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish319.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish321.6 ft. MGO - General Observation - CONNECTIONS AT BOTH 3 AND 9 O'CLOCK IN MH321.6 ft. AMH - Downstream Manhole, Survey Ends - 05 0898

Observation photos (8)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    19.8 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - BROKEN CONNECTION

    23.4 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - BROKEN CONNECTION

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    84 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: NO - AT CONNECTION

    131.1 ft. - Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: NO - AT CONNECTION

  • Tap Break-In Intruding, at 01 o'clock, -, -, within 8 inches of joint: NO, 6", 1"

    305.9 ft. - Tap Break-In Intruding, at 01 o'clock, -, -, within 8 inches of joint: NO, 6", 1"

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    317.2 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (32)

DistanceCodeObservation
178.1TB
321.6MGOCONNECTIONS AT BOTH 3 AND 9 O'CLOCK IN MH
0MWM
150.8TF
120.4TFC
5DAGS
166TFC
262.6TFC
131.1FMAT CONNECTION
211.6TFC
87.3TFA
321.6AMH05 0898
0AMH05 0899
319.4DAGS
295.4TFC
70.1TFUNKNOWN
19.8SSS
0MWL
87.3FM
131.4TB
5CM
292.8TF
23.4TFDBROKEN CONNECTION
319.4SSS
226.6TB
317.2FM
0MGOCONNECTION AT MH 3 O'CLOCK
319.4CM
84.6TB
242.3TF
84FM
305.9TBI

Properties (6)

additional_info
SC398406
custom_field_two
2
customer
LACSD
datetime
2019-11-18T23:07:18-08:00
documentation
PROPIPE
is_lateral_inspection
false