Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 2, 2019, 12:36 PM
  • Section#1_01 0286_01 0285__1222019__I0275R.mp4

Date
12/02/2019
W/O
0784198
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00219
PipeID
P01334
Time
4:36 AM
Certificate
1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0275R
Sewer Name
01 STANFORD AVENUE TRUNK
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Maintenance Related
Project
20191202MDM_STANFORD_AVENUE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
01 0286
Downstream MH
01 0285
Dir. of Survey
Downstream
Length Surveyed
298 ft.
Total Length
298 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
3322
O&M Rating
13
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole 01 0286 to 01 0285
MH: 01 0286MH: 01 0285downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:55AM0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - MH CONN 9:00 ACTIVE0 ft. MGO - General Observation - MH CONN 6:00 ACTIVE42.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB54.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - STUB94.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB106.9 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN138.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - STUB146.4 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE-95% ROOTS146.4 ft. RMC - Roots Medium Connection, from 10 to 12 o'clock, 5 %, within 8 inches of joint: YES189.6 ft. RMC - Roots Medium Connection, from 08 to 11 o'clock, 25 %, within 8 inches of joint: YES189.6 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE-95% ROOTS191.2 ft. RMJ - Roots Medium Joint, from 07 to 09 o'clock, 10 %, within 8 inches of joint: YESR193.1 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - STUB229.9 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN242.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB292.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - STUB294.8 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN298 ft. AMH - Downstream Manhole, Survey Ends - 5:25AM

Observation photos (2)

  • Roots Medium Connection, from 08 to 11 o'clock, 25 %, within 8 inches of joint: YES

    189.6 ft. - Roots Medium Connection, from 08 to 11 o'clock, 25 %, within 8 inches of joint: YES

  • Roots Medium Joint, from 07 to 09 o'clock, 10 %, within 8 inches of joint: YESR

    191.2 ft. - Roots Medium Joint, from 07 to 09 o'clock, 10 %, within 8 inches of joint: YESR

Observations (21)

DistanceCodeObservation
0MWL
298AMH5:25AM
0AMH4:55AM
191.2RMJ
42.1TFCSTUB
146.4TFDACTIVE-95% ROOTS
229.9TFOPEN
0MWM
106.9TFOPEN
0MGOMH CONN 9:00 ACTIVE
54.5TFCSTUB
294.8TFOPEN
242.3TFCSTUB
193.1TFCSTUB
146.4RMC
94.7TFCSTUB
189.6RMC
189.6TFDACTIVE-95% ROOTS
0MGOMH CONN 6:00 ACTIVE
138.2TFCSTUB
292.6TFCSTUB

Properties (5)

additional_info
POST ROOT EVALUATION ONLY
customer
LACSD
datetime
2019-12-02T04:36:00-08:00
documentation
MARTIN,REVELES,OLIVER 111,INACIO
is_lateral_inspection
false