Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 26, 2019, 08:36 AM
  • Section#1_05 2016_05 1055__11262019__I0271.mp4

Date
11/26/2019
W/O
0798048
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00488
PipeID
P06289
Time
12:36 AM
Certificate
1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0271
Sewer Name
05 MONETA EXTENSION TRUNK, SECTION 1
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
21
Purpose
Routine Assessment
Project
20191126MDM_MONETA_EXTENSION_TRUNK_SECTION_1
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
05 2016
Downstream MH
05 1055
Dir. of Survey
Downstream
Length Surveyed
20.7 ft.
Total Length
20.7 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 05 2016 to 05 1055
MH: 05 2016MH: 05 1055downstream0 ft. AMH - Upstream Manhole, Survey Begins - 1:20AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 0 %of cross sectional area - NO FLOW1 ft. MGO - General Observation - STOPLOG IN PLACE2 ft. MMC - Material Change, Vitrified clay pipe - PIPE IS NOT RCP4.2 ft. FC - Fracture Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES - HAIRLINE14.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start20.1 ft. MGO - General Observation - ZOOM 20'20.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish20.7 ft. AMH - Downstream Manhole, Survey Ends - 1:50AM

Observation photos (6)

  • General Observation -  STOPLOG IN PLACE

    1 ft. - General Observation - STOPLOG IN PLACE

  • Material Change, Vitrified clay pipe - PIPE IS NOT RCP

    2 ft. - Material Change, Vitrified clay pipe - PIPE IS NOT RCP

  • Fracture Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES - HAIRLINE

    4.2 ft. - Fracture Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES - HAIRLINE

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    14.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - ZOOM 20'

    20.1 ft. - General Observation - ZOOM 20'

  • Downstream Manhole, Survey Ends - 1:50AM

    20.7 ft. - Downstream Manhole, Survey Ends - 1:50AM

Observations (10)

DistanceCodeObservation
0AMH1:20AM
1MGOSTOPLOG IN PLACE
0MWM
20.1MGOZOOM 20'
20.7AMH1:50AM
0MWLNO FLOW
20.1DAGS
2MMCPIPE IS NOT RCP
14.1DAGS
4.2FCHAIRLINE

Properties (6)

custom_field_three
HAIRLINE FRACTURE-PIPE IS VCP NOT RCP
custom_field_two
4
customer
LACSD
datetime
2019-11-26T00:36:37-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false