Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 24, 2019, 09:37 AM
  • 22 0641_22 0640 _05242019_025011.mp4

Date
05/24/2019
W/O
766521
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00827
PipeID
P16989
Time
2:37 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6541
Sewer Name
22 SUNFLOWER TRUNK
City
SAN DIMAS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
22
Purpose
Routine Assessment
Project
WO_766521_TV22166_MAY2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0640
Downstream MH
22 0641
Dir. of Survey
Upstream
Length Surveyed
334.8 ft.
Total Length
334.8 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
330
O&M Index
2
O&M Quick
2L00
O&M Rating
132
Overall Index
2
Overall Quick
Overall Rating
462
Pipe schematic from manhole 22 0640 to 22 0641
MH: 22 0640MH: 22 0641upstream0 ft. AMH - Upstream Manhole, Survey Ends - 22 06411.6 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 12 O'CLOCK1.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.6 ft. SSS - Surface Spalling, from 04 to 08 o'clock, within 8 inches of joint: YES, Finish1.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish82.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"109.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"135.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"159.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"184.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"212.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"232.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"261.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"281.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"309.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"325.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"332.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start332.6 ft. SSS - Surface Spalling, from 04 to 08 o'clock, within 8 inches of joint: YES, Start332.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start334.8 ft. MWM - Water Mark, 30 %of cross sectional area334.8 ft. AMH - Downstream Manhole, Survey Begins - 22 0640334.8 ft. MGO - General Observation - COCKROACHES IN MANHOLE334.8 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 04 to 08 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Spalling, from 04 to 08 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
2.2SAP
199.3TFA
150.3TFC
252.7TFA
122.5TFA
2.2SSS
333.2MGOACTIVE CONNECTION AT MH 12 O'CLOCK
2.2DAGS
334.8AMH22 0641
53.3TFA
333.2SAP
224.9TFA
333.2SSS
9TFC
101.9TFA
24.9TFC
0MWM
0AMH22 0640
0MGOCOCKROACHES IN MANHOLE
73.3TFA
175.1TFC
0MWL
333.2DAGS

Properties (6)

additional_info
SC378156
custom_field_two
2
customer
LACSD
datetime
2019-05-24T02:37:32-07:00
documentation
PRO PIPE
is_lateral_inspection
false