Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 15, 2019, 05:09 AM
  • 05 0767_05 0766 _03142019_222204.mp4

Date
03/14/2019
W/O
755955
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00553
PipeID
P05994
Time
10:09 PM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6475
Sewer Name
05 MANCHESTER-VERMONT DIVERSION EXTENSION TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_755955_TV05272_MAR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 0767
Downstream MH
05 0766
Dir. of Survey
Downstream
Length Surveyed
354.9 ft.
Total Length
354.9 ft.
Structural Index
3
Structural Quick
4M3M
Structural Rating
626
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
626
Pipe schematic from manhole 05 0767 to 05 0766
MH: 05 0767MH: 05 0766downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 07670 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.4 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start351.2 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish353 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish353 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish354.9 ft. AMH - Downstream Manhole, Survey Ends - 05 0766

Observation photos (1)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    5.4 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
0AMH05 0767
5.4FM
0MWM
351.2FM
354.9AMH05 0766
353SSS
353CM
2CM
2SSS
0MWL

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-03-14T22:09:45-07:00
documentation
PROPIPE
is_lateral_inspection
false