Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 14, 2019, 05:44 AM
  • 05 0777_05 0776 _03132019_230710.mp4

Date
03/13/2019
W/O
755955
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00553
PipeID
P06005
Time
10:44 PM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6474
Sewer Name
05 MANCHESTER-VERMONT DIVERSION EXTENSION TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_755955_TV05272_MAR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 0777
Downstream MH
05 0776
Dir. of Survey
Downstream
Length Surveyed
405.9 ft.
Total Length
405.9 ft.
Structural Index
3
Structural Quick
423O
Structural Rating
408
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
408
Pipe schematic from manhole 05 0777 to 05 0776
MH: 05 0777MH: 05 0776downstream0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 07772 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.8 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start402.6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish403 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish403 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish405.9 ft. AMH - Downstream Manhole, Survey Ends - 05 0776

Observation photos (1)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    5.8 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
403CM
2CM
0MWL
402.6FM
0MWM
403SSS
5.8FM
0AMH05 0777
405.9AMH05 0776
2SSS

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-03-13T22:44:51-07:00
documentation
PROPIPE
is_lateral_inspection
false