Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 22, 2019, 02:37 PM
  • 29 0132_29 0131 _10222019_072952.mp4

Date
10/22/2019
W/O
792800
Weather
Dry
Operator/Surveyor
E. RUIZ
Sewer ID
Z01116
PipeID
P24024
Time
7:37 AM
Certificate
U-116-07001919
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7104
Sewer Name
29 SPRING STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
02
Purpose
Routine Assessment
Project
RFIR_WO_792800_TV29062_OCT2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0132
Downstream MH
29 0131
Dir. of Survey
Downstream
Length Surveyed
317.9 ft.
Total Length
317.9 ft.
Structural Index
3
Structural Quick
5243
Structural Rating
136
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
136
Pipe schematic from manhole 29 0132 to 29 0131
MH: 29 0132MH: 29 0131downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 01320 ft. MWM - Water Mark, 15 %of cross sectional area52.2 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4" - BROKEN IN LATRAL53.9 ft. CM - Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES55.2 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"68.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES71.4 ft. FM - Fracture Multiple, from 04 to 08 o'clock, within 8 inches of joint: YES74.3 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES75.6 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"116.8 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"118.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: NO121.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES136 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES148 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start167 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"205 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"253 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 4"307.3 ft. FM - Fracture Multiple, from 03 to 09 o'clock, within 8 inches of joint: YES307.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish309.8 ft. B - Broken, from 07 to 05 o'clock, within 8 inches of joint: YES311.4 ft. H - Hole, at 12 o'clock, within 8 inches of joint: NO313.5 ft. B - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES317.9 ft. MGO - General Observation - COCKROACHES IN D/S MH317.9 ft. AMH - Downstream Manhole, Survey Ends - 29 131

Observation photos (23)

  • Water Level, 5 %of cross sectional area

    0 ft. - Water Level, 5 %of cross sectional area

  • Water Mark, 15 %of cross sectional area

    0 ft. - Water Mark, 15 %of cross sectional area

  • Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4" - BROKEN IN LATRAL

    52.2 ft. - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4" - BROKEN IN LATRAL

  • Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

    53.9 ft. - Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"

    55.2 ft. - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    68.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 04 to 08 o'clock, within 8 inches of joint: YES

    71.4 ft. - Fracture Multiple, from 04 to 08 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    74.3 ft. - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"

    75.6 ft. - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"

    116.8 ft. - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: NO

    118.2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: NO

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    121.3 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    136 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    148 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"

    167 ft. - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"

    205 ft. - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 4"

    253 ft. - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 4"

  • Fracture Multiple, from 03 to 09 o'clock, within 8 inches of joint: YES

    307.3 ft. - Fracture Multiple, from 03 to 09 o'clock, within 8 inches of joint: YES

  • Broken, from 07 to 05 o'clock, within 8 inches of joint: YES

    309.8 ft. - Broken, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Hole, at 12 o'clock, within 8 inches of joint: NO

    311.4 ft. - Hole, at 12 o'clock, within 8 inches of joint: NO

  • Broken, from 08 to 04 o'clock, within 8 inches of joint: YES

    313.5 ft. - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN D/S MH

    317.9 ft. - General Observation - COCKROACHES IN D/S MH

  • Downstream Manhole, Survey Ends - 29 131

    317.9 ft. - Downstream Manhole, Survey Ends - 29 131

Observations (25)

DistanceCodeObservation
311.4H
118.2CM
167TF
253TB
68.5CM
121.3FM
0MWL
52.2TFBROKEN IN LATRAL
313.5B
71.4FM
136CM
148CM
0AMH29 0132
307.3FM
317.9MGOCOCKROACHES IN D/S MH
55.2TFC
116.8TFC
205TFC
75.6TF
0MWM
53.9CM
317.9AMH29 131
74.3CM
309.8B
307.3CM

Properties (6)

additional_info
SC378808
custom_field_two
2
customer
LACSD
datetime
2019-10-22T07:37:00-07:00
documentation
PRO PIPE
is_lateral_inspection
false