Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 8, 2019, 08:12 AM
  • F 0071B_F 0071A _11082019_002129.mp4

Date
11/08/2019
W/O
793321
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00035
PipeID
P10158
Time
12:12 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7157
Sewer Name
F JOINT OUTFALL F - UNIT 3A
City
BELLFLOWER
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39
Purpose
Routine Assessment
Project
RFIR_WO_793321_TV02313_OCT2019
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
66 in.
Width
66 in.
Upstream MH
F 0071B
Downstream MH
F 0071A
Dir. of Survey
Downstream
Length Surveyed
2 ft.
Total Length
2 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole F 0071B to F 0071A
MH: F 0071BMH: F 0071Adownstream0 ft. MWL - Water Level, 65 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - F 0071B0 ft. MWM - Water Mark, 90 %of cross sectional area2 ft. MSA - Survey Abandoned - VIEW OF SIPHON DOWNLEG2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES2 ft. SSS - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: NO

Observation photos (2)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: NO

    2 ft. - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: NO

Observations (6)

DistanceCodeObservation
0MWL
2MSAVIEW OF SIPHON DOWNLEG
2SAP
2SSS
0AMHF 0071B
0MWM

Properties (6)

additional_info
SC378692
custom_field_two
3
customer
LACSD
datetime
2019-11-08T00:12:04-08:00
documentation
PROPIPE
is_lateral_inspection
false