Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 8, 2019, 11:16 AM
  • F 0068_F 0067 _11112019_124104.mp4

Date
11/08/2019
W/O
792838
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00035
PipeID
P10153
Time
3:16 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7158
Sewer Name
F JOINT OUTFALL F - UNIT 3A
City
BELLFLOWER
Loc. details
Railway
Location Code
L
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39
Purpose
Routine Assessment
Project
RFIR_WO_792838_TV02363_OCT2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Width
60 in.
Upstream MH
F 0068
Downstream MH
F 0067
Dir. of Survey
Downstream
Length Surveyed
246.1 ft.
Total Length
246.1 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole F 0068 to F 0067
MH: F 0068MH: F 0067downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - F 00680 ft. MWM - Water Mark, 55 %of cross sectional area10.9 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start11 ft. MGO - General Observation - HEAVY STEAM IN MH81.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start235.4 ft. MGO - General Observation - CABLE CAUGHT ON DEBRIS245.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish245.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish246.1 ft. AMH - Downstream Manhole, Survey Ends - F 0067

Observation photos (2)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    10.9 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    81.2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
245.2SSS
81.2SSS
0MWL
246.1AMHF 0067
0MGOCONNECTION AT MH 3 O'CLOCK
0AMHF 0068
235.4MGOCABLE CAUGHT ON DEBRIS
0MWM
11MGOHEAVY STEAM IN MH
245.2SAP
10.9SAP

Properties (6)

additional_info
SC378693
custom_field_two
3
customer
LACSD
datetime
2019-11-08T03:16:08-08:00
documentation
PROPIPE
is_lateral_inspection
false