Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 27, 2019, 04:45 AM
  • 29 0738_29 0317 _03262019_221538.mp4

Date
03/26/2019
W/O
755793
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z01017
PipeID
P24350
Time
9:45 PM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6498
Sewer Name
29 PACIFIC COAST HIGHWAY SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_755793_TV29085_MAR2019
Sewer Type
Gravity
Material
CON
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0317
Downstream MH
29 0738
Dir. of Survey
Upstream
Length Surveyed
165.3 ft.
Total Length
165.3 ft.
Structural Index
2
Structural Quick
4435
Structural Rating
101
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
103
Pipe schematic from manhole 29 0317 to 29 0738
MH: 29 0317MH: 29 0738upstream0 ft. AMH - Upstream Manhole, Survey Ends - 29 07382.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish4.3 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 80 % MAG4.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish8.8 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES37.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4", 8" - OPEN44.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES46.7 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES59.7 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES63.2 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - 35% GREASE/OPEN77.3 ft. FS - Fracture Spiral, from 10 to 11 o'clock, within 8 inches of joint: YES79.7 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN86.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"90.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES98.2 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES114.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN116.2 ft. FH2 - Fracture Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES140.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"159.3 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES162.4 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES162.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start163.3 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 80% MAG163.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start165.3 ft. MWM - Water Mark, 10 %of cross sectional area165.3 ft. AMH - Downstream Manhole, Survey Begins - 29 0317165.3 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (11)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    2.9 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    6 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES

    49.1 ft. - Fracture Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    67.1 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    74.8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 10 to 11 o'clock, within 8 inches of joint: YES

    88 ft. - Fracture Spiral, from 10 to 11 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    105.6 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    118.6 ft. - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    120.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    156.5 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

Observations (26)

DistanceCodeObservation
161SZ80 % MAG
156.5FM
0MWM
6FM
162.6SAP
0AMH29 0317
85.6TBOPEN
67.1CL
161SSS
79TFA
2.9FM
120.9FL
74.8FL
102.1TFD35% GREASE/OPEN
165.3AMH29 0738
49.1FH2
88FS
118.6CL
0MWL
2SZ80% MAG
127.4TFOPEN
2.9SAP
50.5TFOPEN
105.6CL
24.8TFA
2SSS

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-03-26T21:45:46-07:00
documentation
PROPIPE