Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 26, 2019, 04:34 AM
  • 29 0341_29 0340 _03252019_222131.mp4

Date
03/25/2019
W/O
755793
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z01017
PipeID
P24361
Time
9:34 PM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6494
Sewer Name
29 PACIFIC COAST HIGHWAY SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_755793_TV29085_MAR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0341
Downstream MH
29 0340
Dir. of Survey
Downstream
Length Surveyed
251.8 ft.
Total Length
251.8 ft.
Structural Index
3
Structural Quick
4E3I
Structural Rating
365
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
365
Pipe schematic from manhole 29 0341 to 29 0340
MH: 29 0341MH: 29 0340downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 03412 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 70% MAG2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES19.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES25.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start44.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"67.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish75.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"75.2 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES75.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES85.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES100 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES107.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"133.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"140.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES161.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES166 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"168 ft. FM - Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES168.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"179.9 ft. FM - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES185.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start216.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"224 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"249 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish249 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 65% MAG249 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish250 ft. MGO - General Observation - ROACHES @ MH250.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish251.8 ft. AMH - Downstream Manhole, Survey Ends - 29 0340

Observation photos (12)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    6.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    19.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    25.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    75.2 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    75.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    85.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    100 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    140.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    161.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

    168 ft. - Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

    179.9 ft. - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    185.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (33)

DistanceCodeObservation
75.5CM
185.7FM
2SZ70% MAG
216.1TFC
44.5TFC
251.8AMH29 0340
100CM
85.2FM
249CM
19.1FM
168FM
2SSS
0MWM
75.2TFA
0MWL
250.6FM
133.2TFC
140.9FM
161.6FM
250MGOROACHES @ MH
107.3TFA
25.4FM
168.9TFC
224TFA
6.4FM
179.9FM
249SZ65% MAG
249SSS
2CM
0AMH29 0341
166TFA
75.2CL
67.7FM

Properties (4)

customer
LACSD
datetime
2019-03-25T21:34:01-07:00
documentation
PROPIPE
is_lateral_inspection
false