Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 18, 2019, 06:18 AM
  • B 1348_B 1347 _09172019_233140.mp4

Date
09/17/2019
W/O
787657
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01126
PipeID
P25243
Time
11:18 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6934
Sewer Name
B JOINT OUTFALL B - UNIT 6J
City
PASADENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
08
Purpose
Routine Assessment
Project
WO_787657_TV30028_SEP2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
B 1348
Downstream MH
B 1347
Dir. of Survey
Downstream
Length Surveyed
302 ft.
Total Length
302 ft.
Structural Index
2
Structural Quick
3122
Structural Rating
7
O&M Index
2
O&M Quick
2P00
O&M Rating
170
Overall Index
2
Overall Quick
Overall Rating
177
Pipe schematic from manhole B 1348 to B 1347
MH: B 1348MH: B 1347downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 13484.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start9.1 ft. CS - Crack Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES66.3 ft. CM - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES88.8 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES157.9 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 6"172.2 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start299.9 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish300.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish302 ft. AMH - Downstream Manhole, Survey Ends - B 1347

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    4.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES

    9.1 ft. - Crack Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

    66.3 ft. - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    88.8 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
299.9DSC
300.2DAGS
157.9TB
302AMHB 1347
9.1CS
0MWL
172.2DSC
88.8CL
0MWM
0AMHB 1348
4.4DAGS
66.3CM

Properties (6)

additional_info
SC378533
custom_field_two
4
customer
LACSD
datetime
2019-09-17T23:18:30-07:00
documentation
PROPIPE
is_lateral_inspection
false