Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 22, 2019, 07:55 PM
  • B 1320_B 1319 _10222019_130208.mp4

Date
10/22/2019
W/O
787657
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01126
PipeID
P25215
Time
12:55 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7068
Sewer Name
B JOINT OUTFALL B - UNIT 6J
City
PASADENA
Loc. details
Woods
Location Code
E
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
12
Purpose
Routine Assessment
Project
WO_787657_TV30028_SEP2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
22 in.
Width
22 in.
Upstream MH
B 1320
Downstream MH
B 1319
Dir. of Survey
Downstream
Length Surveyed
35.8 ft.
Total Length
35.8 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
2
Overall Quick
Overall Rating
3
Pipe schematic from manhole B 1320 to B 1319
MH: B 1320MH: B 1319downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 13200 ft. MWL - Water Level, 25 %of cross sectional area9.3 ft. CS - Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES16.6 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start35 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish35.8 ft. AMH - Downstream Manhole, Survey Ends - B 1319

Observation photos (2)

  • Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES

    9.3 ft. - Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    16.6 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
16.6RFJ
35RFJ
0MWM
35.8AMHB 1319
0AMHB 1320
9.3CS
0MWL

Properties (6)

additional_info
SC378668
custom_field_two
4
customer
LACSD
datetime
2019-10-22T12:55:58-07:00
documentation
PROPIPE
is_lateral_inspection
false