Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 10, 2019, 05:37 AM
  • B 1444_B 1443 _09092019_225543.mp4

Date
09/09/2019
W/O
787657
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01126
PipeID
P25157
Time
10:37 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6927
Sewer Name
B JOINT OUTFALL B - UNIT 6J
City
PASADENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
03
Purpose
Routine Assessment
Project
WO_787657_TV30028_SEP2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
B 1444
Downstream MH
B 1443
Dir. of Survey
Downstream
Length Surveyed
87.7 ft.
Total Length
87.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
412B
O&M Rating
36
Overall Index
2
Overall Quick
Overall Rating
36
Pipe schematic from manhole B 1444 to B 1443
MH: B 1444MH: B 1443downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 14440 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - CAPPED CONN. 3 O'CLOCK4.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start86.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish87.7 ft. AMH - Downstream Manhole, Survey Ends - B 1443

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    4.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
0MWL
4.9DAGS
86.4DAGS
0AMHB 1444
0MWM
87.7AMHB 1443
0MGOCAPPED CONN. 3 O'CLOCK

Properties (6)

additional_info
SC378525
custom_field_two
4
customer
LACSD
datetime
2019-09-09T22:37:34-07:00
documentation
PROPIPE
is_lateral_inspection
false