Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 6, 2019, 07:17 AM
  • B 1417_B 1416 _09062019_003346.mp4

Date
09/06/2019
W/O
787657
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01126
PipeID
P25129
Time
12:17 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6924
Sewer Name
B JOINT OUTFALL B - UNIT 6J
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
04
Purpose
Routine Assessment
Project
WO_787657_TV30028_SEP2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Width
16 in.
Upstream MH
B 1417
Downstream MH
B 1416
Dir. of Survey
Downstream
Length Surveyed
265.6 ft.
Total Length
265.6 ft.
Structural Index
3
Structural Quick
4132
Structural Rating
10
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
11
Pipe schematic from manhole B 1417 to B 1416
MH: B 1417MH: B 1416downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 14170 ft. MWL - Water Level, 15 %of cross sectional area3.4 ft. CM - Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES4.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"6.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"51 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"53.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"53.7 ft. RFC - Roots Fine Connection, from 09 to 10 o'clock54.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start79.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES100.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"103.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"108.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"150.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"153.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"200.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"202.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"250.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"252.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"263.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish265.6 ft. AMH - Downstream Manhole, Survey Ends - B 1416

Observation photos (4)

  • Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

    3.4 ft. - Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Roots Fine Connection, from 09 to 10 o'clock

    53.7 ft. - Roots Fine Connection, from 09 to 10 o'clock

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    54.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    79.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
103.4TFC
108.3TB
4.4TFC
153.1TFC
53.7RFC
200.1TFC
252.7TFC
0MWM
53.4TF
6.5TFC
150.4TFC
263.8CM
51TFC
79.7FM
265.6AMHB 1416
0AMHB 1417
202.9TFC
54.9CM
100.9TF
0MWL
3.4CM
250.4TF

Properties (6)

additional_info
SC378521
custom_field_two
3
customer
LACSD
datetime
2019-09-06T00:17:43-07:00
documentation
PROPIPE
is_lateral_inspection
false