Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 11, 2019, 08:10 AM
  • B 1385_B 1384 _09112019_011959.mp4

Date
09/11/2019
W/O
787657
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01126
PipeID
P25097
Time
1:10 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6928
Sewer Name
B JOINT OUTFALL B - UNIT 6J
City
PASADENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
08
Purpose
Routine Assessment
Project
WO_787657_TV30028_SEP2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Width
16 in.
Upstream MH
B 1385
Downstream MH
B 1384
Dir. of Survey
Downstream
Length Surveyed
99.2 ft.
Total Length
99.2 ft.
Structural Index
3
Structural Quick
3C00
Structural Rating
57
O&M Index
2
O&M Quick
2C00
O&M Rating
38
Overall Index
3
Overall Quick
Overall Rating
95
Pipe schematic from manhole B 1385 to B 1384
MH: B 1385MH: B 1384downstream0 ft. MGO - General Observation - CONNECTION AT 3 O'CLOCK0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 13850 ft. MWM - Water Mark, 35 %of cross sectional area2.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start3.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"15.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"99.2 ft. AOC - Drop Connection, Survey Ends - B 138499.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish99.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"99.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
99.2AOCB 1384
3.6CM
0MGOCONNECTION AT 3 O'CLOCK
0MWL
0AMHB 1385
99.2CM
12.4TF
15.5TF
99.2TF
99.2DAGS
0MWM
2.3DAGS

Properties (6)

additional_info
SC378526
custom_field_two
3
customer
LACSD
datetime
2019-09-11T01:10:06-07:00
documentation
PROPIPE
is_lateral_inspection
false