Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 11, 2019, 08:51 AM
  • B 1383_B 1382 _09112019_021048.mp4

Date
09/11/2019
W/O
787657
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01126
PipeID
P25095
Time
1:51 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6928
Sewer Name
B JOINT OUTFALL B - UNIT 6J
City
PASADENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
08
Purpose
Routine Assessment
Project
WO_787657_TV30028_SEP2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Width
16 in.
Upstream MH
B 1383
Downstream MH
B 1382
Dir. of Survey
Downstream
Length Surveyed
295.8 ft.
Total Length
295.8 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
174
O&M Index
2
O&M Quick
312K
O&M Rating
121
Overall Index
2
Overall Quick
Overall Rating
295
Pipe schematic from manhole B 1383 to B 1382
MH: B 1383MH: B 1382downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 13833 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"8.3 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 4"23.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"30.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"73.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"84.6 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 4"121.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"171.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"174.7 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 4"176.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"198.9 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 4"222 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"232.2 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 4"234.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"274.7 ft. RPP - Repair Patch, from 02 to 04 o'clock, within 8 inches of joint: NO - CONCRETE274.7 ft. RFC - Roots Fine Connection, at 04 o'clock276.3 ft. TBD - Tap Break-In Defective, at 03 o'clock, -, , within 8 inches of joint: NO, 6"277.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"279.1 ft. RFC - Roots Fine Connection, at 03 o'clock279.8 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"293.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish293.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish295.8 ft. AMH - Downstream Manhole, Survey Ends - B 1382295.8 ft. MGO - General Observation - CONNECTION AT 3 O'CLOCK

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Repair Patch, from 02 to 04 o'clock, within 8 inches of joint: NO - CONCRETE

    274.7 ft. - Repair Patch, from 02 to 04 o'clock, within 8 inches of joint: NO - CONCRETE

  • Roots Fine Connection, at 04 o'clock

    274.7 ft. - Roots Fine Connection, at 04 o'clock

  • Tap Break-In Defective, at 03 o'clock, -,  , within 8 inches of joint: NO, 6"

    276.3 ft. - Tap Break-In Defective, at 03 o'clock, -, , within 8 inches of joint: NO, 6"

  • Roots Fine Connection, at 03 o'clock

    279.1 ft. - Roots Fine Connection, at 03 o'clock

Observations (29)

DistanceCodeObservation
121.6TFC
295.8AMHB 1382
274.7RPPCONCRETE
222TFC
176.7TF
23.1TFC
232.2TB
73.5TF
279.1RFC
198.9TB
174.7TB
295.8MGOCONNECTION AT 3 O'CLOCK
3DAGS
293.9DAGS
277.5TFC
30.3TF
0MWM
274.7RFC
8.3TB
0MWL
171.7TF
84.6TB
0AMHB 1383
279.8TB
5TBA
4.2CM
234.7TFC
276.3TBD
293.9CM

Properties (6)

additional_info
SC378526
custom_field_two
3
customer
LACSD
datetime
2019-09-11T01:51:52-07:00
documentation
PROPIPE
is_lateral_inspection
false