Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 17, 2019, 07:34 AM
  • B 1379_B 1378 _09172019_004026.mp4

Date
09/17/2019
W/O
787657
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01126
PipeID
P25091
Time
12:34 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6933
Sewer Name
B JOINT OUTFALL B - UNIT 6J
City
PASADENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
08
Purpose
Routine Assessment
Project
WO_787657_TV30028_SEP2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Rectangular
Height
15 in.
Width
15 in.
Upstream MH
B 1379
Downstream MH
B 1378
Dir. of Survey
Downstream
Length Surveyed
46 ft.
Total Length
46 ft.
Structural Index
3
Structural Quick
3800
Structural Rating
24
O&M Index
2
O&M Quick
2800
O&M Rating
16
Overall Index
3
Overall Quick
Overall Rating
40
Pipe schematic from manhole B 1379 to B 1378
MH: B 1379MH: B 1378downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 13793.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start38.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"42.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish42.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish46 ft. AMH - Downstream Manhole, Survey Ends - B 1378

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0MWM
0MWL
4.6CM
42.9CM
46AMHB 1378
3.4DAGS
42.9DAGS
0AMHB 1379
38.6TFC

Properties (6)

additional_info
SC378532
custom_field_two
3`
customer
LACSD
datetime
2019-09-17T00:34:10-07:00
documentation
PROPIPE
is_lateral_inspection
false