Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 17, 2019, 08:19 AM
  • B 1376_B 1375 _09172019_013026.mp4

Date
09/17/2019
W/O
787657
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01126
PipeID
P25088
Time
1:19 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6933
Sewer Name
B JOINT OUTFALL B - UNIT 6J
City
PASADENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
08
Purpose
Routine Assessment
Project
WO_787657_TV30028_SEP2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
B 1376
Downstream MH
B 1375
Dir. of Survey
Downstream
Length Surveyed
120.2 ft.
Total Length
120.2 ft.
Structural Index
3
Structural Quick
3C00
Structural Rating
66
O&M Index
2
O&M Quick
322D
O&M Rating
52
Overall Index
3
Overall Quick
Overall Rating
118
Pipe schematic from manhole B 1376 to B 1375
MH: B 1376MH: B 1375downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 13760 ft. MWM - Water Mark, 35 %of cross sectional area4.5 ft. RMJ - Roots Medium Joint, from 03 to 04 o'clock, 5 %, within 8 inches of joint: YESR4.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start37.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 4"39.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"39.7 ft. MGO - General Observation - LIGHT STEAM IN SEWER86.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"87.7 ft. RMC - Roots Medium Connection, at 10 o'clock, 10 %, within 8 inches of joint: NO88.7 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"105.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 4"116.8 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 4"117 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish117 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish120.2 ft. AMH - Downstream Manhole, Survey Ends - B 1375120.2 ft. MGO - General Observation - CONNECTION AT 3 O'CLOCK

Observation photos (4)

  • Roots Medium Joint, from 03 to 04 o'clock, 5 %, within 8 inches of joint: YESR

    4.5 ft. - Roots Medium Joint, from 03 to 04 o'clock, 5 %, within 8 inches of joint: YESR

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    4.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Connection, at 10 o'clock, 10 %, within 8 inches of joint: NO

    87.7 ft. - Roots Medium Connection, at 10 o'clock, 10 %, within 8 inches of joint: NO

Observations (18)

DistanceCodeObservation
39.7TFC
0MWL
116.8TB
0AMHB 1376
86.3TF
39.7MGOLIGHT STEAM IN SEWER
117DAGS
120.2AMHB 1375
117CM
88.7TBA
4.5RMJ
120.2MGOCONNECTION AT 3 O'CLOCK
105.1TB
6.4CM
0MWM
37.9TFC
87.7RMC
4.5DAGS

Properties (6)

additional_info
SC378532
custom_field_two
3
customer
LACSD
datetime
2019-09-17T01:19:03-07:00
documentation
PROPIPE
is_lateral_inspection
false