Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 17, 2019, 09:59 AM
  • B 1362_B 1361 _09172019_031446.mp4

Date
09/17/2019
W/O
787657
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01126
PipeID
P25074
Time
2:59 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6933
Sewer Name
B JOINT OUTFALL B - UNIT 6J
City
PASADENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
08
Purpose
Routine Assessment
Project
WO_787657_TV30028_SEP2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
B 1362
Downstream MH
B 1361
Dir. of Survey
Downstream
Length Surveyed
264.2 ft.
Total Length
264.2 ft.
Structural Index
3
Structural Quick
3925
Structural Rating
37
O&M Index
2
O&M Quick
2I00
O&M Rating
104
Overall Index
2
Overall Quick
Overall Rating
141
Pipe schematic from manhole B 1362 to B 1361
MH: B 1362MH: B 1361downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 13620 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start30.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"32.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"64 ft. CS - Crack Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES80.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"82.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"122.3 ft. CS - Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES130.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"133.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"144.7 ft. CM - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES145.6 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"159.7 ft. CS - Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES180.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"183.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"187.2 ft. CS - Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES215 ft. CS - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES220.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start230.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"233.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"262.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish262.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish264.2 ft. AMH - Downstream Manhole, Survey Ends - B 1361

Observation photos (8)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

    64 ft. - Crack Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES

    122.3 ft. - Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

    144.7 ft. - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES

    159.7 ft. - Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES

    187.2 ft. - Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

    215 ft. - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    220.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (25)

DistanceCodeObservation
145.6TB
82.9TFC
220.1CM
80.4TF
183.3TFC
64CS
144.7CM
159.7CS
130.7TFC
133.1TFC
262.4CM
215CS
230.9TFC
187.2CS
233.5TF
0AMHB 1362
0MWM
122.3CS
180.7TF
2.4DAGS
32.5TFC
262.6DAGS
30.1TFC
0MWL
264.2AMHB 1361

Properties (6)

additional_info
SC378532
custom_field_two
3
customer
LACSD
datetime
2019-09-17T02:59:43-07:00
documentation
PROPIPE
is_lateral_inspection
false