Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 23, 2019, 08:27 AM
  • B 1361_B 1360 _09232019_015556.mp4

Date
09/23/2019
W/O
787657
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01126
PipeID
P25073
Time
1:27 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6940
Sewer Name
B JOINT OUTFALL B - UNIT 6J
City
PASADENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
08
Purpose
Routine Assessment
Project
WO_787657_TV30028_SEP2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
B 1361
Downstream MH
B 1360
Dir. of Survey
Downstream
Length Surveyed
265.2 ft.
Total Length
265.2 ft.
Structural Index
3
Structural Quick
3300
Structural Rating
9
O&M Index
3
O&M Quick
3221
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
17
Pipe schematic from manhole B 1361 to B 1360
MH: B 1361MH: B 1360downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 13610 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area8.7 ft. CM - Crack Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES11.2 ft. CM - Crack Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES13.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start17.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"19.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"67.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"68.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"70 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"80 ft. RML - Roots Medium Lateral, from 08 to 11 o'clock, 10 %, within 8 inches of joint: YES81.1 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 4"117.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"120.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 4"166 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"168.4 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 4" - COLLAPSED221.4 ft. RML - Roots Medium Lateral, from 02 to 05 o'clock, 10 %, within 8 inches of joint: NO221.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"224.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"263.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish265.2 ft. ACOM - Cleanout Mainline, Survey Ends - B 1360

Observation photos (6)

  • Crack Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

    8.7 ft. - Crack Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES

    11.2 ft. - Crack Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    13.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Lateral, from 08 to 11 o'clock, 10 %, within 8 inches of joint: YES

    80 ft. - Roots Medium Lateral, from 08 to 11 o'clock, 10 %, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 4" - COLLAPSED

    168.4 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 4" - COLLAPSED

  • Roots Medium Lateral, from 02 to 05 o'clock, 10 %, within 8 inches of joint: NO

    221.4 ft. - Roots Medium Lateral, from 02 to 05 o'clock, 10 %, within 8 inches of joint: NO

Observations (22)

DistanceCodeObservation
0AMHB 1361
11.2CM
221.4RML
68.1TB
166TFC
8.7CM
265.2ACOMB 1360
0MWM
70TFC
263.1CM
120.1TB
117.7TF
168.4TFDCOLLAPSED
81.1TB
67.6TFC
80RML
17.1TF
13.6CM
224.3TFC
221.7TF
19.6TFC
0MWL

Properties (6)

additional_info
SC378539
custom_field_two
3
customer
LACSD
datetime
2019-09-23T01:27:36-07:00
documentation
PROPIPE
is_lateral_inspection
false