Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 14, 2019, 12:03 PM
  • 18 0969_18 0968_11142019_041139.mp4

Date
11/14/2019
W/O
0798462
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00716
PipeID
P14819
Time
4:03 AM
Certificate
1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1307
Sewer Name
18 WORSHAM CREEK TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
11
Purpose
Routine Assessment
Project
20191114MDM_WORSHAM_CREEK_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
18 0969
Downstream MH
18 0968
Dir. of Survey
Downstream
Length Surveyed
174.3 ft.
Total Length
174.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3211
O&M Rating
7
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 18 0969 to 18 0968
MH: 18 0969MH: 18 0968downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:10AM0 ft. MGO - General Observation - MH CONN 900 ACTIVE0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area18.6 ft. MGO - General Observation - 8" VCP-PVCP72 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6" - Open129.1 ft. RFC - Roots Fine Connection, from 09 to 10 o'clock, within 8 inches of joint: NO - 3%129.1 ft. TBD - Tap Break-In Defective, at 10 o'clock, -, , within 8 inches of joint: NO, 6" - Open-90%136.8 ft. TBD - Tap Break-In Defective, at 01 o'clock, -, , within 8 inches of joint: NO, 6" - Active-95% ROOTS174.3 ft. AMH - Downstream Manhole, Survey Ends - 4:25AM

Observation photos (1)

  • General Observation - 8" VCP-PVCP

    18.6 ft. - General Observation - 8" VCP-PVCP

Observations (10)

DistanceCodeObservation
18.6MGO8" VCP-PVCP
129.1RFC3%
0AMH4:10AM
0MGOMH CONN 900 ACTIVE
72TBOpen
174.3AMH4:25AM
136.8TBDActive-95% ROOTS
129.1TBDOpen-90%
0MWL
0MWM

Properties (5)

customer
LACSD
datetime
2019-11-14T04:03:37-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false
lining
PVCP