Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 25, 2018, 01:39 PM
  • 1_02 1793_02 1637_Shot_SI_TapeLocation_POST_25042018_180509.mpg

Date
04/25/2018
W/O
200326
Weather
Dry
Operator/Surveyor
OSCAR VILLARREAL
Sewer ID
Z00292
PipeID
P04138
Time
6:39 AM
Certificate
U-1113-06019665
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Jetting
Media Label
01
Sewer Name
02 MONTEREY PARK RELIEF TRUNK
City
MONTERREY PARK CA.
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Pre-Rehabilitation Survey
Project
MONTEREY_PARK_RELIEF_TRUNK_REHABILITATION
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
02 1793
Downstream MH
02 1637
Dir. of Survey
Downstream
Length Surveyed
164.7 ft.
Total Length
164.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 02 1793 to 02 1637
MH: 02 1793MH: 02 1637downstream0 ft. MWL - Water Level, 0 % of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - MH 17930 ft. AMH - Upstream Manhole, Survey Begins - mh 17930 ft. MWL - Water Level, 0 % of cross sectional area25.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, 4", within 8 inches of joint: YES25.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, 6", within 8 inches of joint: YES50.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, 4", within 8 inches of joint: YES68 ft. TFA - Tap Factory Made Active, at 10 o'clock, 4", within 8 inches of joint: YES68.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, 4", within 8 inches of joint: YES89.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, 4", within 8 inches of joint: YES92 ft. TFA - Tap Factory Made Active, at 12 o'clock, 4", within 8 inches of joint: YES118.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, 4", within 8 inches of joint: YES120.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, 4", within 8 inches of joint: YES164.7 ft. AMH - Downstream Manhole, Survey Ends - MH 1637164.8 ft. AMH - Downstream Manhole, Survey Ends - mh 1637

Observations (15)

DistanceCodeObservation
92TFA
120.1TFA
164.7AMHMH 1637
25.6TFA
68.9TFA
0MWL
0AMHMH 1793
50.8TFC
68TFA
164.8AMHmh 1637
0AMHmh 1793
89.8TFA
118.3TFA
25.1TFA
0MWL

Properties (3)

customer
LACSD
datetime
2018-04-25T06:39:01-07:00
is_lateral_inspection
false