Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 5, 2019, 08:37 AM
  • 18 0795_18 0794 _11052019_004158.mp4

Date
11/05/2019
W/O
792842
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00706
PipeID
P14653
Time
12:37 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6326
Sewer Name
18 SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
City
SANTA FE SPRINGS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Routine Assessment
Project
RFIR_WO_792842_TV18197_OCT2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
18 0794
Downstream MH
18 0795
Dir. of Survey
Upstream
Length Surveyed
93.1 ft.
Total Length
93.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2C00
O&M Rating
38
Overall Index
2
Overall Quick
Overall Rating
38
Pipe schematic from manhole 18 0794 to 18 0795
MH: 18 0794MH: 18 0795upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 07950.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0.2 ft. MGO - General Observation - CONNECTION AT 9 O'CLOCK38.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"93.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start93.1 ft. AMH - Downstream Manhole, Survey Begins - 18 079493.1 ft. MWM - Water Mark, 20 %of cross sectional area93.1 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Downstream Manhole, Survey Begins - 18 0794

    0 ft. - Downstream Manhole, Survey Begins - 18 0794

Observations (8)

DistanceCodeObservation
54.7TF
0DAGS
93DAGS
0AMH18 0794
0MWM
92.9MGOCONNECTION AT 9 O'CLOCK
93.1AMH18 0795
0MWL

Properties (6)

additional_info
SC365763
custom_field_two
4
customer
LACSD
datetime
2019-11-05T00:37:05-08:00
documentation
PROPIPE
is_lateral_inspection
false