Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 20, 2018, 07:28 AM
  • 05 0095_05 0094 _12192018_233748.mp4

Date
12/19/2018
W/O
740131
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00431
PipeID
P05385
Time
11:28 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6253
Sewer Name
05 DISTRICT #5 MAIN TRUNK
City
HAWTHRONE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_740015_TV05147_DEC2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
42 in.
Upstream MH
05 0095
Downstream MH
05 0094
Dir. of Survey
Downstream
Length Surveyed
243.5 ft.
Total Length
243.5 ft.
Structural Index
4
Structural Quick
5H3I
Structural Rating
374
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
374
Pipe schematic from manhole 05 0095 to 05 0094
MH: 05 0095MH: 05 0094downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 00950 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0.3 ft. MGO - General Observation - MAG COAT2.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11.6 ft. SRV - Surface Reinforcement Visible, at 04 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY THROUGHOUT243.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish243.5 ft. AMH - Downstream Manhole, Survey Ends - 05 0094243.5 ft. SRV - Surface Reinforcement Visible, at 04 o'clock, within 8 inches of joint: YES, Finish243.5 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, at 04 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY THROUGHOUT

    11.6 ft. - Surface Reinforcement Visible, at 04 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY THROUGHOUT

Observations (11)

DistanceCodeObservation
0MWL
11.6SRVSPORADICALLY THROUGHOUT
2.8SAP
243.5SAP
243.5AMH05 0094
0MWM
0AMH05 0095
0.3MGOMAG COAT
243.5SRV
0MGOCONNECTION AT MH 9 O'CLOCK
243.5MGOCONNECTION AT MH 9 O'CLOCK

Properties (6)

additional_info
SC365486
custom_field_two
2
customer
LACSD
datetime
2018-12-19T23:28:14-08:00
documentation
PROPIPE
is_lateral_inspection
false