Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 8, 2016, 11:59 AM
  • 05 0351_05 0350_08012016_035943.mp4

Date
01/08/2016
W/O
536429
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00432
PipeID
P05565
Time
3:59 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3068
Sewer Name
05 DISTRICT #5 MAIN RELIEF TRUNK
City
HAWTHORNE
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
WO_536429_TV05014_DEC2015
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
05 0351
Downstream MH
05 0350
Dir. of Survey
Downstream
Length Surveyed
437.7 ft.
Total Length
437.7 ft.
Structural Index
3
Structural Quick
3P2P
Structural Rating
435
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
439
Pipe schematic from manhole 05 0351 to 05 0350
MH: 05 0351MH: 05 0350downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 03510 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start436.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish436.5 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish437.7 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK437.7 ft. AMH - Downstream Manhole, Survey Ends - 05 0350437.7 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    437.7 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (11)

DistanceCodeObservation
437.7MGOACTIVE CONNECTION AT MH 3 O'CLOCK
2SSS
0MGOCOCKROACHES IN MANHOLE
437.7AMH05 0350
0MWL
0AMH05 0351
436.5SSS
436.5SAP
2SAP
0MWM
437.7MGOCOCKROACHES IN MANHOLE

Properties (6)

additional_info
SC224840
custom_field_two
3
customer
LACSD
datetime
2016-01-08T03:59:29-08:00
documentation
PRO PIPE
is_lateral_inspection
false