Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 8, 2016, 10:20 AM
  • 05 0353_05 0352_08012016_022058.mp4

Date
01/08/2016
W/O
536429
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00432
PipeID
P05567
Time
2:20 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3068
Sewer Name
05 DISTRICT #5 MAIN RELIEF TRUNK
City
HAWTHORNE
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
WO_536429_TV05014_DEC2015
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
05 0353
Downstream MH
05 0352
Dir. of Survey
Downstream
Length Surveyed
438.3 ft.
Total Length
438.3 ft.
Structural Index
3
Structural Quick
5N3P
Structural Rating
795
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
799
Pipe schematic from manhole 05 0353 to 05 0352
MH: 05 0353MH: 05 0352downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 03530 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.1 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES71.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY THROUGHOUT431.8 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish433.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish433.3 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish438 ft. MGO - General Observation - COCKROACHES IN MANHOLE438.3 ft. AMH - Downstream Manhole, Survey Ends - 05 0352

Observation photos (5)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES

    2.1 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY THROUGHOUT

    71.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY THROUGHOUT

  • General Observation - COCKROACHES IN MANHOLE

    438 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (13)

DistanceCodeObservation
431.8SRV
71.1SRVSPORADICALLY THROUGHOUT
2.1SAP
0MWL
438MGOCOCKROACHES IN MANHOLE
2SSS
433.3SSS
0MWM
0AMH05 0353
433.3SAP
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
438.3AMH05 0352
2.1SRV

Properties (6)

additional_info
SC224840
custom_field_two
2
customer
LACSD
datetime
2016-01-08T02:20:41-08:00
documentation
PRO PIPE
is_lateral_inspection
false