Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 8, 2016, 08:21 AM
  • 05 0355_05 0354_08012016_011615.mp4

Date
01/08/2016
W/O
536429
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00432
PipeID
P05569
Time
12:21 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3068
Sewer Name
05 DISTRICT #5 MAIN RELIEF TRUNK
City
HAWTHORNE
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
WO_536429_TV05014_DEC2015
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
05 0355
Downstream MH
05 0354
Dir. of Survey
Downstream
Length Surveyed
437.6 ft.
Total Length
437.6 ft.
Structural Index
3
Structural Quick
3P2P
Structural Rating
435
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
439
Pipe schematic from manhole 05 0355 to 05 0354
MH: 05 0355MH: 05 0354downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 05 03552 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start436.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish436.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE436.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish437.6 ft. AMH - Downstream Manhole, Survey Ends - 05 0354

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    436.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (10)

DistanceCodeObservation
0MWM
0MWL
0MGOCOCKROACHES IN MANHOLE
436.2SSS
2SSS
436.2MGOCOCKROACHES IN MANHOLE
436.2SAP
0AMH05 0355
2SAP
437.6AMH05 0354

Properties (6)

additional_info
SC206429
custom_field_two
3
customer
LACSD
datetime
2016-01-08T00:21:44-08:00
documentation
PRO PIPE
is_lateral_inspection
false