Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 8, 2016, 09:07 AM
  • 05 2547_05 0355_08012016_010814.mp4

Date
01/08/2016
W/O
536429
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00432
PipeID
P05570
Time
1:07 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3068
Sewer Name
05 DISTRICT #5 MAIN RELIEF TRUNK
City
HAWTHORNE
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
WO_536429_TV05014_DEC2015
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
05 2547
Downstream MH
05 0355
Dir. of Survey
Downstream
Length Surveyed
156.6 ft.
Total Length
156.6 ft.
Structural Index
3
Structural Quick
3E2E
Structural Rating
155
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
159
Pipe schematic from manhole 05 2547 to 05 0355
MH: 05 2547MH: 05 0355downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 05 25472 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start155 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish155 ft. MGO - General Observation - COCKROACHES IN MANHOLE155 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish156.6 ft. AMH - Downstream Manhole, Survey Ends - 05 0355

Observation photos (3)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    155 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (10)

DistanceCodeObservation
155SSS
0MWM
156.6AMH05 0355
0MWL
2SAP
155MGOCOCKROACHES IN MANHOLE
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
2SSS
0AMH05 2547
155SAP

Properties (6)

additional_info
SC224840
custom_field_two
3
customer
LACSD
datetime
2016-01-08T01:07:54-08:00
documentation
PRO PIPE
is_lateral_inspection
false