Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 30, 2018, 11:43 AM
  • 17 0015_17 0014 _30012018_041153.mp4

Date
01/30/2018
W/O
685314
Weather
Dry
Operator/Surveyor
K. ADAME
Sewer ID
Z00668
PipeID
P21489
Time
3:43 AM
Certificate
U-0817-07009000
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4859
Sewer Name
17 DISTRICT #17 MAIN TRUNK
City
PASADENA, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 17
Page No.
07
Purpose
Routine Assessment
Project
WO_685314_TV17010_FEB2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
17 0015
Downstream MH
17 0014
Dir. of Survey
Downstream
Length Surveyed
396.8 ft.
Total Length
396.8 ft.
Structural Index
4
Structural Quick
5143
Structural Rating
35
O&M Index
2
O&M Quick
312O
O&M Rating
163
Overall Index
2
Overall Quick
Overall Rating
198
Pipe schematic from manhole 17 0015 to 17 0014
MH: 17 0015MH: 17 0014downstream0 ft. AMH - Upstream Manhole, Survey Begins - 17 00150 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area26.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start81.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"90.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES92 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"93.5 ft. FM - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES101.8 ft. CM - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES113.7 ft. CM - Crack Multiple, from 08 to 09 o'clock, within 8 inches of joint: YES123.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"136.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES138.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"160.4 ft. FM - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES161.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"188.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"189.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES194.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start199.6 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"232 ft. RML - Roots Medium Lateral, at 02 o'clock, 45 %, within 8 inches of joint: YES - ROOTS232 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"240.2 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"268 ft. HVV - Hole Void Visible, from 02 to 04 o'clock, within 8 inches of joint: NO279.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"296.8 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"313.4 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"324.8 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"337.1 ft. TBC - Tap Break-In Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"345.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"361.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"369.8 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"377.8 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"390 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"396 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish396.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish396.8 ft. AMH - Downstream Manhole, Survey Ends - 17 0014

Observation photos (12)

  • Upstream Manhole, Survey Begins - 17 0015

    0 ft. - Upstream Manhole, Survey Begins - 17 0015

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    26.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    90.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

    93.5 ft. - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

    101.8 ft. - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 09 o'clock, within 8 inches of joint: YES

    113.7 ft. - Crack Multiple, from 08 to 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    136.1 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    160.4 ft. - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    189.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    194.1 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Lateral, at 02 o'clock, 45 %, within 8 inches of joint: YES - ROOTS

    232 ft. - Roots Medium Lateral, at 02 o'clock, 45 %, within 8 inches of joint: YES - ROOTS

  • Hole Void Visible, from 02 to 04 o'clock, within 8 inches of joint: NO

    268 ft. - Hole Void Visible, from 02 to 04 o'clock, within 8 inches of joint: NO

Observations (36)

DistanceCodeObservation
390TB
90.4CM
396.8CM
123.1TF
81.1TFC
232RMLROOTS
232TB
189.6FM
199.6TBC
0AMH17 0015
161.3TF
396.8AMH17 0014
0MWM
377.8TB
279.1TB
93.5FM
337.1TBC
240.2TBC
101.8CM
26.1DAGS
138.4TF
194.1CM
313.4TBC
160.4FM
92TFC
296.8TBC
136.1CM
188.3TFC
0MWL
324.8TB
396DAGS
361.3TB
113.7CM
345.3TB
369.8TBC
268HVV

Properties (6)

additional_info
SC346883
custom_field_two
2
customer
LACSD
datetime
2018-01-30T03:43:02-08:00
documentation
PRO-PIPE
is_lateral_inspection
false