Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 14, 2019, 09:24 AM
  • 16 0619_16 0618_10142019_014258.mp4

Date
10/14/2019
W/O
792814
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00664
PipeID
P13669
Time
2:24 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7034
Sewer Name
16 PASADENA EAST-WEST INTERCEPTOR TRUNK
City
PASADENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
09
Purpose
Routine Assessment
Project
WO_792814_TV16030_OCT2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
16 0619
Downstream MH
16 0618
Dir. of Survey
Downstream
Length Surveyed
459.4 ft.
Total Length
459.4 ft.
Structural Index
3
Structural Quick
3Q2Q
Structural Rating
452
O&M Index
2
O&M Quick
2Q00
O&M Rating
182
Overall Index
2
Overall Quick
Overall Rating
634
Pipe schematic from manhole 16 0619 to 16 0618
MH: 16 0619MH: 16 0618downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 16 06190 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 70% MAG2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start456.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish456.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish457 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish457 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 70% MAG459.4 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE459.4 ft. AMH - Downstream Manhole, Survey Ends - 16 0618459.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4.7 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    459.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (16)

DistanceCodeObservation
0MWL
456.2DAGS
457SSS
457SZ70% MAG
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
456.2SAP
0AMH16 0619
459.4MGOCONN @ MH 9 O'CLOCK/ACTIVE
4.7SAP
2SSS
0MWM
459.4AMH16 0618
2SZ70% MAG
459.4MGOCOCKROACHES IN MANHOLE
2DAGS
0MGOCOCKROACHES IN MANHOLE

Properties (6)

additional_info
SC378703
custom_field_two
2
customer
LACSD
datetime
2019-10-14T02:24:05-07:00
documentation
PRO PIPE
is_lateral_inspection
false