Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 21, 2019, 08:51 AM
  • 16 0610_16 0609_10212019_010746.mp4

Date
10/21/2019
W/O
792814
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00664
PipeID
P13660
Time
1:51 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7049
Sewer Name
16 PASADENA EAST-WEST INTERCEPTOR TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
10
Purpose
Routine Assessment
Project
WO_792814_TV16030_OCT2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
16 0610
Downstream MH
16 0609
Dir. of Survey
Downstream
Length Surveyed
404.3 ft.
Total Length
404.3 ft.
Structural Index
3
Structural Quick
3O2O
Structural Rating
397
O&M Index
2
O&M Quick
2O00
O&M Rating
160
Overall Index
2
Overall Quick
Overall Rating
557
Pipe schematic from manhole 16 0610 to 16 0609
MH: 16 0610MH: 16 0609downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 06100 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 65% MAG2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6.3 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start78.6 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN118 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"182.7 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"238.9 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"402 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish402 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 65% MAG403.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE403.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish403.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish403.1 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE404.3 ft. AMH - Downstream Manhole, Survey Ends - 16 0609

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    6.3 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    403.1 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (20)

DistanceCodeObservation
402SSS
403.1MGOCOCKROACHES IN MANHOLE
182.7TB
403.1DAGS
404.3AMH16 0609
118TBA
6.3SAP
2SZ65% MAG
0AMH16 0610
2SSS
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
0MWL
402SZ65% MAG
238.9TBA
2DAGS
403.1SAP
0MGOCOCKROACHES IN MANHOLE
78.6TBOPEN
0MWM
403.1MGOCONN @ MH 9 O'CLOCK/ACTIVE

Properties (6)

additional_info
SC378718
custom_field_two
2
customer
LACSD
datetime
2019-10-21T01:51:52-07:00
documentation
PRO PIPE
is_lateral_inspection
false