Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 4, 2019, 11:20 AM
  • 15 0612_15 0611_11042019_033046.mp4

Date
11/04/2019
W/O
792806
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00601
PipeID
P12547
Time
3:20 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6324
Sewer Name
15 DOUBLE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_792806_TV15205_OCT2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0612
Downstream MH
15 0611
Dir. of Survey
Downstream
Length Surveyed
137.1 ft.
Total Length
137.1 ft.
Structural Index
3
Structural Quick
4D3D
Structural Rating
185
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
185
Pipe schematic from manhole 15 0612 to 15 0611
MH: 15 0612MH: 15 0611downstream0 ft. MGO - General Observation - ABANONED MH0 ft. AMH - Upstream Manhole, Survey Begins - 15 06120 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area3.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.5 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start21.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"23.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"81.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"96.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"137.1 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish137.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish137.1 ft. AMH - Downstream Manhole, Survey Ends - 15 0611137.1 ft. MGO - General Observation - CONNECTION AT 3 O'CLOCK

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    7.5 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
137.1FM
0MGOABANONED MH
96.4TF
0AMH15 0612
21.9TF
7.5FM
3.4SAP
81.1TF
0MWM
0MWL
137.1SAP
137.1AMH15 0611
23.9TF
137.1MGOCONNECTION AT 3 O'CLOCK

Properties (6)

additional_info
SC365761
custom_field_two
2
customer
LACSD
datetime
2019-11-04T03:20:46-08:00
documentation
PROPIPE
is_lateral_inspection
false